Hardware manual

Chapter 2 Connection to a PLC
2-104
3.4.4 C200H
α
(Communication Board) Settings
Write the Communication Board setting items for the System Settings Area using a peripheral
tool (such as Procon).
System Settings
Area
Port A Port B
Item Setting
DM6555 DM6550 Standard Setting/Individual Setting
(*1)
Same setting as the
MICRO/I
Mode PLC Link Mode
DM6556 DM6551 Communication parameters for
when the previous item is set to
Individual.
Same setting as the
MICRO/I
DM6557 DM6552 Transmission Delay 0 msec
DM6558 DM6553 Unit No. Same setting as the
MICRO/I
(*1) Standard settings
Baud rate: 9600bps
Data Bits: 7 bits
Stop Bits: 2 bits
Parity: Even
Set DIP switch SW1 to the 4 side (4 line).
Set DIP switch SW2 to ON to turn the termination resistor setting ON.
Refer to the Communication Board manual for details.