Hardware manual
3 Omron
2-103
Chap.2
3.4.3 CPU Unit RS-232C Link I/F Settings (CS1 Series)
Write the RS-232C I/F setting items for the System Settings Area using a peripheral tool (such
as Procon).
Channel Item Setting
Optional/Initial Setting (*1) Set to 1 for Optional Setting
Serial Communication mode Set to PLC Link
Data Bits
Stop Bits
160
Parity
Use the same settings as for the
MICRO/I.
161 Port Communication Speed Use the same settings as for the
MICRO/I.
162 In the case of No Protocol Mode Do not set
163 Unit No. Set to the same as the MICRO/I PLC Link
Station Number.
164 In the case of No Protocol Mode Do not set
(*1) Initial settings
Baud rate: 9600 bps
Data Bits: 7 bits
Stop Bits: 2 bits
Parity: Even
Refer to the PLC manual for details.
For the CS1 Series, set switch number 5 on the CPU Unit setting switch to OFF to enable you
to make your own communication settings.