Instruction Manual

OFF position
(Default)
Default OFF position configures conventional mode, ON position enables Heat Pump mode
Select Conventional or Heat Pump Mode using Dipswitch 1-2
Single-Stage Operation- Dipswitch 1-1 set to ON position
If Y2 or W2 is left unconnected or is unavailable from the thermostat set SW1-1 to the ON position. This configures single stage operation of RMF-
CA200-V1(A) simulating multiple stage operation using temperature differential based on W1 / Y1 call and run time.
Thermostat Conventional Mode
Connections
Pin Signal Description
1 TC Common (IN) Transformer
2 C
Common (Out) To
Thermostat
3 TR 24 VAC (IN) Transformer
4 R 24 VAC (IN) Thermostat
5 Y2 Stage 2 Cooling
6 Y1 Stage 1 Cooling
7 W2 Stage 2 Heat
8 W1 Stage 1 Heat
9 W3 Stage 3 Heat
10 G Fan
11 O
DO NOT CONNECT TO
INTERFACE
12 EO Error Output (Out)
Thermostat Heat Pump Mode
Connections
Pin Signal Description
1 TC Common (IN) Transformer
2 C
Common (Out) To
Thermostat
3 TR 24 VAC (IN) Transformer
4 R 24 VAC (OUT) to Thermostat
5 Y2
Heat Pump Stage 2
Heat/Cool
6 Y1
Heat Pump Stage 1
Heat/Cool
7 AUX1 N/A
8 OB
Heat pump Heat / Cool
mode
9 AUX2 Stage 4 Heat
10 G Fan
11 O
DO NOT CONNECT TO
INTERFACE
12 EO Error Output (Out)
Example2:
Conventional Two-Stage Cooling and Heating -
Dipswitch 1-1 set to OFF position (default position)
RMF-CA200-V1(A) operates in dual stage heat / cool
mode using thermostat signals W1, W2, Y1, Y2, and
fan signal (G). G1, G2 and G3 are available but not
required.
Example 3: Heat Pump Mode Operation - Dipswitch 1-1 set to ON position
If Y2 or W2 is left unconnected or is unavailable from the thermostat set SW1-1 to the ON
position. This configures single stage operation of RMF-CA100-V1(A) simulating multiple
stage operation using temperature differential based on W1 / Y1 call and run time.
In single stage operation Y2, W2 and W3 signals
are not used
TC
C
TR
R
-
Y1
-
W1
-
G
-
EO
TC
C
TR
R
Y2
Y1
W2
W1
-
G
-
EO
TC
C
TR
R
Y2
Y1
-
OB
-
G
-
EO
Two Stage Conventional Interface Connection
Single Stage Conventional Interface Connection
Heat Pump Mode Interface Connection