User's Manual
Triple e vacuation
in
6easysteps
S tep 1 Ev ac uate the sys t e m t o 1000 microns from b ot h servi c e val ves.
To measure the vacuum a vacuum g aug e must be used at
all times - do not u se a system man ifold gau ge
S t e p 2 Break the vacuum with O FN to 14 PSIG
S t ep 3 Ev acu a te to 500 m i cron s
S tep 4 Repeat Step 2
S t ep 5 Evacuate to the lowest pressure that the pump will achieve
(20 0 mi crons f or a mini mum of 1 hour)
S t e p 6 T he rise test mu st then be carried out for a minim um of 30 minutes
Pa ge 10