Service manual
3
SPECIFICATIONS
2
SLZ-A09AR.TH SLZ-A12AR.TH
Indoor model
Function
Power supply
Single phase
230V, 50Hz
600/540/480
10
0.18
40
0.014
0.18
PK6V15-LA
4
38/35/32
650/580/530
3
10
10
10
MPPC
Cooling
91
Heating
92
Single phase
230V, 50Hz
660/600/540
10
0.23
52
0.014
0.23
PK6V20-LE
4
39/37/34
690/630/570
3
10
10
10
MPPC
Cooling
94
Heating
95
Air flow (High/Med./Low)
Power outlet
Running current ✽1
Power input Rated frequency
Dew prevention heater
Power factor ✽1
Fan motor current ✽1
Model
Winding
resistance (at20:)
Width
Height
Depth
Weight
Air direction
Sound level(High/Med./Low)
Fan speed(High/Med./Low)
Fan speed regulator
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Thermistor RT13(at25:)
Remote controller model
K /h
A
A
W
(kW)
%
A
"
mm(in)
mm(in)
mm(in)
kg
dB(A)
rpm
k"
k"
k"
Electrical
data
Fan
motor
Special
remarks
Capacity
Dimensions
WHT-BLK : 407 BLK-BLU : 55
BLU-YLW : 31 YLW-BRN : 30
BRN-RED : 165
UNIT : 570(22-7/16) PANEL : 650(25-9/16)
UNIT : 208(8-3/16) PANEL : 20(13/16)
UNIT : 570(22-7/16) PANEL : 650(25-9/16)
UNIT : 16.5 PANEL : 3
WHT-BLK : 384 BLK-BLU : 111
BLU-YLW : 49 YLW-BRN : 46
BRN-RED : 311
SLZ-A18AR.TH
Single phase
230V, 50Hz
660/600/540
20
0.24
53
0.014
0.24
PK6V20-LF
4
40/38/35
710/650/590
3
10
10
10
MPPC
Cooling
97
Heating
97
WHT-BLK : 317 BLK-BLU : 88
BLU-YLW : 52 YLW-BRN : 45
BRN-RED : 301
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor D.B. 27: W.B. 19:
Outdoor D.B. 35: W.B. 24:
Heating : Indoor D.B. 20: W.B. 15:
Outdoor D.B. 7: W.B. 6:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency.
1.5+ 440V
250V 3.15A
MSBPC20 12V 250"
POWER SUPPLY : 3P TO OUTDOOR UNIT : 4P
G4A-1A-E-PS 12V DC
145:i2:
240V AC 15W
INDOOR UNIT
Item
Model
Indoor fan capacitor
Fuse
Vane motor
Terminal block
Contactor
Indoor fan motor thermal fuse
Cord Heater
SLZ-A09AR.TH SLZ-A12AR.TH SLZ-A18AR.TH
(C1)
(F11)
(MV)
(TB)
(52C)
(H2)
Specifications and rating conditions of main electric parts
OC302-1.qxp 04.3.17 11:49 AM Page 3