Service manual

8 9
Piping Length
(
one way
)
Charged
Factory
Service Ref. 100ft 110ft 120ft 130ft 140ft 150ft 160ft 165ft
30m 33m 37m 40m 43m 46m 49m 50m
PUZ-HA30NHA4
PUZ-HA36NHA4
194 oz 200 oz 206 oz 212 oz 218 oz 224 oz 230 oz 237 oz 195 oz
5.5 kg 5.7 kg 5.9 kg 6.0 kg 6.2 kg 6.4 kg 6.6 kg 6.7 kg
180ft 200ft 210ft 230ft 245ft
55m 61m 64m 70m 75m
242 oz 254 oz 260 oz 272 oz 280 oz
6.9 kg 7.2 kg 7.4 kg 7.7 kg 7.9 kg 5.5 kg
Longer pipe than 100 ft
,
additional charge is required.
Service Ref.
Compressor model
(
)
Winding Registance
U-V
U-W
W-V
(
at 20°C
,
68°F
)
PUZ-HA30NHA4
PUZ-HA36NHA4
ANB33FJEMT
0.188
0.188
0.188
5-1. REFILLING REFRIGERANT CHARGE (R410A : oz, kg)
5-2. COMPRESSOR TECHNICAL DATA
5
DATA
5-3. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUZ-HA30NHA4
PUZ-HA36NHA4
COOLING
MODE
HEATING
52
SPL(dB)
53
LINE
5ft
3.3ft
MICROPHONE
UNIT
GROUND