Start and finish of test run [For outdoor controller board]
Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2.
2Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3Turn off SW4-1 to finish the test run.
There may be a faint knocking sound around the machine room after power is supplied,
but this is no problem with product because the linear expansion pipe is just moving to
adjust opening pulse.
There may be a knocking sound around the machine room for several seconds after com-
pressor starts operating. But this is not a problem with product because the check valve
itself generates the sound because pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
TEST
RUN
COOL
,
Test run [for IR wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M".
1 Turn on the main power to the unit.
2 Press the
TEST RUN
button twice continuously.
(Start this operation from the turned off status of remote controller
display.)
TEST RUN
and current operation mode are displayed.
3 Press the
MODE
( ) button to activate
COOL
mode, then
check whether cool air is blown out from the unit.
4 Press the
MODE
( ) button to activate
HEAT
mode, then
check whether warm air is blown out from the unit.
5 Press the
FAN
button and check whether strong air is blown out
from the unit.
6 Press the
VANE
button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Note:
Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.
It is not possible to run in FAN, DRY or AUTO mode.
OFF
1 2
ON
<SW4>
Stop Operation
Cooling Heating