User`s manual

3 - 3 3 - 3
MELSEC-Q
3 DATA USED FOR PROCESS CONTROL INSTRUCTIONS AND HOW TO
SPECIFY DATA
3.2 Local Work Memory
The local work memory is used as a temporary storage area in process control instruction
operation. (Memory used for micro blocks only)
The following instructions use the local work memory.
Instruction name Remarks
S.LLAG (Lead/Lag)
S.D (Differentiation)
S.DED (Dead time)
S.FLT (Standard filter)
S.BUMP (Bump-less transfer)
S.AT1 (Auto tuning)
This stores the midway operation results for the OS itself.
(Cannot be used by the user.)
S.FG (Polygon)
S.IFG (Inverted polygon)
This stores the polygon coordinate value (Xn, Yn) used by
the user. Operations are conducted based on this.
Block diagram
Process control
instruction execution
Data for operation
Data after operation
Local work
memory
Operation result
Input data setting Operation constant setting
Block memory
Ladder diagram
R200R20R100R0S.LLAG
Operation constant setting
Normal ON
Instruction name S.LLAG (Lead/Lag)
Input data head device R0
Block memory head device R100
Operation constant head device R20
Local work memory head device R200
The application of the local work memory changes depending on the used instruction. Refer to the