User`s manual
10 - 13 10 - 13
MELSEC-Q
10 COMPENSATION OPERATION INSTRUCTIONS
Control data
(1) Data specified in S.ENG instruction
Specified position Symbol Name Recommended range
*1
Unit Data format
Standard
value
Store
Input data
S1
+0
+1
E1 Input value -999999 to 999999 %
Real
number
U
Block
memory
D1
+0
+1
BW Output value (-999999 to 999999)
Real
number
S
S2
+0
+1
RH
Engineering
value upper
limit
-999999 to 999999
Real
number
100.0 U
Operation
constant
+2
+3
RL
Engineering
value lower
limit
-999999 to 999999
Real
number
0.0 U
*1: The data of the item(s) where the values within the recommended range are given in the parentheses are stored by the system.
Users cannot set the data.
Processing contents
(1) The S.ENG instruction performs the following operation.
E1
RL
100
BW
RH
RL (E1 0 to 100%)
ERROR
• When an operation error occurs Error code: 4100