User`s manual

9 - 97 9 - 97
MELSEC-Q
9 CONTROL OPERATION INSTRUCTIONS
9.23 Program Setting Device (S.PGS)
Usable devices
Internal devices
(System, user)
MELSECNET/H
direct J
\
Setting
data
Bit Word
File
register
Bit Word
Intelligent
function
module
U
\G
Index
register
Zn
Constant
K, H
Other
S1
D1
S2
D2
S.PGS
S.PGS
Start contact
S1 D1 S2 D2
[Instruction symbol] [Execution condition]
Set data Description
S1
Dummy device
*1
D1
Block memory head device
S2
Dummy device
*1
D2
Loop tag memory head device
*1: Special register SD1506 can be specified as a dummy device.
Functions
Provides a control output according to the SV and MV pattern.
As the output types of the S.PGS instruction, there are three types of the "hold type", "return type"
and "cyclic type".
• Hold type : Output is provided with the SV10 value held.
• Return type : The set value (SV) is set to 0 and the last value is output as the manipulated
value (MV).
• Cyclic type : After SV1 to SV10 have been processed, processing is restarted from SV1 and
the output is provided.