User`s manual
9 - 55 9 - 55
MELSEC-Q
9 CONTROL OPERATION INSTRUCTIONS
Control data
(1) Data specified in S.PHPL instruction
Specified position Symbol Name Recommended range
*1
Unit Data format
Standard
value
Store
Input
data
S1
+0
+1
E1 Input value -999999 to 999999 %
Real
number
U
D1
+0
+1
BW Output value (-999999 to 999999) %
Real
number
S
BB
BB1 Alarm
BB2
Upper limit
alarm
BB3
Lower limit
alarm
BB4
Positive direction
change rate
alarm
Block
memory
+2
BB5
Negative
direction change
rate alarm
b15 b12 b8 b4 b0
B
B
1
(0: Without alarm)
(1: With alarm)
B
B
2
B
B
3
B
B
4
B
B
5
BIN
16bit
S
D2
+1 MODE Operation mode
0 to FFFF
H
b15 b12 b8
b4 b0
L
C
C
L
C
A
L
C
M
M
A
N
A
U
T
C
A
S
C
M
B
C
A
B
C
C
B
C
M
V
C
S
V
BIN
16bit
8
H
S/U
+3 ALM Alarm detection
0 to FFFF
H
b15 b12 b8 b4 b0
S
P
A
H
H
A
SPA
0: Loop RUN
1: Loop STOP
Other
(0: Without alarm)
(1: With alarm)
D
P
P
A
L
L
A
P
H
A
P
L
A
D
P
N
A
BIN
16bit
4000
H
S/U
+4 INH
Alarm detection
inhibition
0 to FFFF
H
b15
b12 b8
b4 b0
E
R
R
I
L
L
I
0: Alarm enable
1: Alarm inhibit
H
H
I
D
P
P
I
P
H
I
P
L
I
D
P
N
I
BIN
16bit
4000
H
S/U
+10
+11
PV Process value (RL to RH)
Real
number
0.0 S
+22
+23
RH
Engineering
value upper limit
-999999 to 999999
Real
number
100.0 U
Loop
tag
memory
*2
+24
+25
RL
Engineering
value lower limit
-999999 to 999999
Real
number
0.0 U
*1: The data of the item(s) where the values within the recommended range are given in the parentheses are stored by the system.
Users cannot set the data.
*2: The loop tag memory and loop tag past value memory occupy a total of 128 words. (Refer to Section 3.3.1 for details.)