Specifications

Q/QnA Serial Communication Driver
GP-Pro EX Device/PLC Connection Manual
22
Setting of External Device
Use the GPP function software by Mitsubishi Electric Corporation to perform the communication settings as
below.
(1) Double-click [PC Parameter] from [Parameter] to select the [I/O Assign Setting] tab.
(2) Click [Type] to select [Intelligent].
(3) Click [Switch Settings] and set as below.
Important Item
When you use 2 types of interface in QJ71C24, please set the total speed of CH1 and CH2 to 115200 or less.
Setting Switch
Setting
Value
Setup Description
Switch 3 07E6 19200/8/With/Odd/1
Switch 4 0005
*1
*1 Set the value according to [Format] to be used.
Mode = Form 5
Switch 5 0000 Station No. = 0
Please refer to the manual of the External Device for more detail on setting description.