User`s manual

10 - 41 10 - 41
MELSEC-Q
10 TROUBLESHOOTING
10.3.14 Troubleshooting when data cannot be communicated via modem
Symptom Cause Corrective action MC
Non
procedure
protocol
Bidirection
al protocol
• A modem initialization error occurs.
• Check the error code and execute
processing accordingly.
• Modem connection channel designation is
not performed.
• Set Modem connection channel
designation.
• Auto modem initialization
cannot be executed.
• There is an error in the switch settings in the
GX Developer.
• Review the switch settings. Set it to match
the local station modem and the TA.
• Communication protocol setting is incorrect.
• Set the communication protocol to MC
protocol, format 5.
• Transmission setting does not match the
external device.
• Review the transmission setting.
• Data cannot be
communicated with GX
Developer supporting the Q
series C24.
• Communication rate does not match the
external device.
• Review the communication rate setting.
• The product is not supported by the GX
Developer.
• Confirm the GX Developer’s S/W version.
• There was an error in the GX Developer
connection system.
• Check the GX Developer’s connection
system.
• Set the connection system on “callback
reception waiting” and connect.
• The GX Developer does not
receive the callback signals
from the Q Series C24.
• There is an error in the GX Developer side’s
modem settings.
• Set the modem’s settings on "Auto
Reception."
• There s an error in the GX Developer’s
connection system.
• Check the GX Developer’s connection
system.
• Correct the Q Series C24’s settings.
• Callback connections from
the GX Developer are
refused by the Q Series
C24.
• There is an error in the connection system’s
telephone No.
• Check the telephone No.
• Change the telephone No. to the data for
callback.
• There is an error in the Q Series C24
setting value.
• Set the callback function designation on the
setting 1 to 3.
• There is an error in the GX Developer’s
connection system.
• Check the GX Developer’s connection
system.
• Check the Q Series C24’s settings.
• When performing Auto
(callback: during fixed/
during designated number)
from the GX Developer,
connection to the Q Series
C24 is refused.
• There is an error in the telephone No. of the
connection system.
• Check the telephone No.
• Change the telephone No. to the data for
callback.
• The timer value for the status of the modem
used or the line is short.
• Adjust each of the timer values for the
callback function on the GX Developer side.
(Line callback cancel wait time, callback
delay time)
It is possible to connect
from the GX Developer, but
callback from the Q Series
C24 cannot be performed.
• There is a problem with the modem
specifications or settings.
• Check the modem’s specifications and
settings.