(7) The following describes how the Q series C24 operates when the
programmable controller CPU monitoring result information cannot be sent to
the external device due to line disconnection or other reasons.
Even if an error occurs while the programmable controller CPU monitoring function is in operation, the ERR LED
does not light up. (This is the same as when using the on-demand function of the MC protocol.)
(a) When the setting for the transmission monitoring time designation (timer 2) is an
infinite wait (0H)
• Reading of monitoring data from the programmable controller CPU stops until the transmission of monitoring
data completes.
• When transmission resumes, reading of monitoring data from the programmable controller CPU resumes
and monitoring data and information are transmitted.
(b) When the setting for the transmission monitoring time designation (timer 2) is other
than an infinite wait (0H)
• A transmission timeout error occurs, monitoring information read from the programmable controller CPU,
and transmission of monitoring information resumes.
• The error code is stored in the programmable controller CPU monitoring function error code storage area
(address: 2205H).
(8) When device data for the programmable controller CPU cannot be read
because of a programmable controller CPU error (hardware failure, etc.), the
error code is stored in the programmable controller CPU monitoring function
error code storage area and the Q series C24 performs the monitoring
processing based on previously read data.
(9) When the monitoring information is transmitted as data using the modem
function, a modem connection error will occur if a modem connection is
requested for the following reasons.
• A connection request by Y11
• A notification-issued request by Y14
If possible, provide a dedicated Q series C24 for using the programmable controller CPU monitoring function.
When using both the programmable controller CPU monitoring function and data communication function with a
single Q series C24 and one of the above modem connection errors occurs, re-execute a connection request in
consideration of the transmission timing set by the user for the programmable controller CPU monitoring function.