User`s manual

63
CHAPTER 2 USING THE PROGRAMMABLE CONTROLLER CPU MONITORING FUNCTION
2
2.3 Settings for Using the Programmable Controller CPU Monitoring Function
(4) Setting items for sending monitoring results
The following is an example of setting items and data transmission when sending the monitoring results of the
programmable controller CPU monitoring function execution to the external device using the non procedure
protocol.
This example shows a case in which the D0 to D3 device information and user frame data are sent by the
edge trigger method using a condition of D0 = 0.
Perform the settings on the "PLC CPU monitoring system setting" screen and the "###" screen of GX
Configurator-SC.
PLC CPU monitoring system setting
Setting the transmission user frames
Setting item Setting data Remarks
Cycle time units min
Settings other than those
listed at left are not required
Cycle time 3
PLC CPU monitoring function Condition agreement
PLC CPU monitoring transmission measure Data transmission
Number of registered word blocks 1
Number of registered bit blocks 0
PLC CPU abnormal monitoring 0
No. 1 block monitoring device
Monitoring device D
Head device No. 0
Read point 4
Condition agreement
transmission
Monitoring condition Edge =
Monitoring condition
value
0
Transmission pointer 49
Output count 3
User frame number
User frame number
User frame number (03H)
User frame number
User frame number
User frame number
User frame number
Transmission frame No. designation 50th
Transmission frame No. designation 51st
Transmission frame No. designation 55th
Transmission frame No. designation 54th
Transmission frame No. designation 53rd
Transmission frame No. designation 52nd
Transmission frame No. designation 56th
Transmission frame No. designation 57th
Transmission frame No. designation 46th
Transmission frame No. designation 49th
Transmission frame No. designation 48th
Transmission frame No. designation 47th
User frame number (02H)
User frame number
User frame number
User frame number
User frame number (B001H)
Set the first block (from D0 to D3)
Set the user frame data (ETX)
Set the user frame data (STX)
Device
data
(D0)
Device
data
(D1)
Device
data
(D2)
Device
data
(D3)
External device
Data sent when the condition D = 0 is satisfied
Number of
registered
points
Device code
Monitoring
head
device
ETX ETX