(g) Monitoring device, head device No., read point (Number of registered points)
When performing device data monitoring or transmission, designate the device range for each block for the
number of blocks designated by number of registered word blocks and number of registered bit blocks (
Page 61, Section 2.3.1 (3) (e)).
*1
*1 The target of device data monitoring for condition agreement transmission is the head device for each block.
Word device designated block: Head word device (for one word)
Bit device designated block: Head bit device (for one bit)
The monitored device is the item that indicates the target device of the corresponding block and designated
with the codes listed in Page 38, Section 2.2.2 (4).
The head device is the data that designates the head of the target device range for the corresponding block.
The read point is the item that indicates the target device range for the corresponding block which designate
points from the head device No. The bit device designates points in word units (1 point = 16 bits)
The methods for designating these data are the same as the designation methods used when reading from
or writing to the device memory, which are described in the MELSEC Communication Protocol Reference
Manual.
Remark
When the user performs the programmable controller CPU monitoring registration, the device will designate either a decimal
or hexadecimal device No. The read points (registration points) are designated as hexadecimal.
However, if this is done by either MC protocol communication (form 1) to 4)) or non procedure protocol communication,
when ASCII-BIN conversion of the communication data has been designated, the head device No. for all devices to be sent
to external devices as the monitoring results will be converted to hexadecimal ASCII data and sent.
(h) Monitoring condition
When condition agreement transmission is designated with the programmable controller CPU monitoring
function ( Page 61, Section 2.3.1 (3) (c)), designate the conditions for transmitting information for the
monitoring condition value ( Page 62, Section 2.3.1 (3) (i)).
(i) Monitoring condition value
When condition agreement transmission is designated with the programmable controller CPU monitoring
function ( Page 61, Section 2.3.1 (3) (c)), this item designates the status/numeric value of the monitoring
condition ( Page 62, Section 2.3.1 (3) (h)).
When the monitoring device is a word device: Designate the monitoring condition value with a numeric value
When the monitoring device is a bit device: Designate the monitoring condition with a numeric value (1/0)
corresponding to ON/OFF.