User`s manual
42
(b) Two transmission methods of the monitoring results are available for the condition
agreement transmission for device monitoring. These include edge triggered
transmission and level triggered transmission.
• Edge triggered transmission
The monitoring conditions registered by the user (conditions for sending monitoring results), the monitoring
condition values and the monitoring information read from the programmable controller CPU are compared.
The monitoring results are sent or notified only once when an agreement of the monitoring conditions is
detected for the first time.
After that, when the monitoring information read from the programmable controller CPU does not match the
monitoring conditions and then it matches the monitoring conditions once again, the monitoring results are sent
or notified.
• Level triggered transmission
The monitoring conditions registered by the user (conditions for sending monitoring results), the monitoring
condition values and the monitoring information read from the programmable controller CPU are compared.
While the monitoring conditions agree, the monitoring results are sent or notified at each cycle time.
(Timing to transmit data)
(c) In the condition agreement transmission for device monitoring, the head device for
each block is the monitoring target for condition monitoring of each block device.
For the condition agreement transmission, the monitoring conditions that can be designated for the device to
be registered by the user and the registration values when designating the monitoring condition are listed in the
table below.
Register the monitoring conditions for the head device of each block using the following table.
Monitoring condition (item to be judged)
Registration value
Valid designated
device
For edge triggered
transmissions
For level triggered
transmissions
Bit Word
Device value or status = device monitoring condition value or status 0001H 0101H
Device value or status device monitoring condition value or status 0002H 0102H
Unsigned
Monitoring device monitoring condition value 0003H 0103H
Monitoring device < monitoring condition value 0004H 0104H
Monitoring device monitoring condition value 0005H 0105H
Monitoring device > monitoring condition value 0006H 0106H
Signed
Monitoring device monitoring condition value 0007H 0107H
Monitoring device < monitoring condition value 0008H 0108H
Monitoring device monitoring condition value 0009H 0109H
Monitoring device > monitoring condition value 000AH 010AH
END ENDEND
Condition agreement
transmission
Cycle time
Sequence program
(conditions matched/not
matched)
External device
Matched
Not matched
Matched
One-block
portion
One-block
portion
Monitoring information
…