User`s manual

407
CHAPTER 17 DEDICATED INSTRUCTIONS
17
17.8 ZP.UINI
17.8.5 Program example
The settings of the Q series C24 installed in the position of I/O No. X/Y00 to X/Y1F are changed as indicated below
when X20 is turned on.
Device
Bit
Description Set value
Position
Specified
value
(S)+3
b0 OFF
CH1
transmission
specifications
setting
Operation setting Independent
07E6H
b1 ON Data bit 8 bits
b2 ON Parity bit Yes
b3 OFF Even/odd parity Odd
b4 OFF Stop bit 1 bit
b5 ON Sum check code Yes
b6 ON Write during RUN Allowed
b7 ON Setting modifications Allowed
b8 to b15 Communication rate setting 19200bps
(S)+4 CH1 communication protocol setting Synchronous setting 0008H
(S)+5
b0 ON
CH2
transmission
specifications
setting
Operation setting Synchronous
07E7H
b1 ON Data bit 8 bits
b2 ON Parity bit Yes
b3 OFF Even/odd parity Odd
b4 OFF Stop bit 1 bit
b5 ON Sum check code Yes
b6 ON Write during RUN Allowed
b7 ON Setting modifications Allowed
b8 to b15 Communication rate setting 19200bps
(S)+6 CH2 communication protocol setting MC protocol format 5 0005H
(S)+7 Station No. setting Station 1 0001H