User`s manual
394
17.6.2 Control data
Remark
● For information about errors caused by incorrect data designated by the user, see Page 396, Section 17.6.4.
● The "Set by" column indicates the following:
• User: Data set by the user before executing the dedicated instruction.
• System: The programmable controller CPU stores execution results of the dedicated instruction.
Device Item Setting data Setting range Set by
(S)+0 Transmission channel
Designate the transmission channel.
1: Channel 1 (CH1 side)
2: Channel 2 (CH2 side)
1, 2 User
(S)+1 Transmission result
The transmission completion result by the PRR instruction is
stored.
0: Normal
Other than 0: Error code
System
(S)+2 CR/LF addition designation
Designate whether or not to add CR/LF to the transmission
data.
0: Do not add CR/LF.
1: Add CR/LF.
0, 1 User
(S)+3 Transmission pointer
Transmission user frame designation area designates from
which the frame number data may be transmitted.
1 to 100 User
(S)+4 Output count Designate the number of user frames to be transmitted. 1 to 100 User