User`s manual
393
CHAPTER 17 DEDICATED INSTRUCTIONS
17
17.6 G(P).PRR
17.6 G(P).PRR
In non procedure protocol communication, this instruction transmits data using a user frame according to the data
specified in the transmission user frame designation area.
17.6.1 Setting data
The file registers of each of the local device and the program cannot be used as the setting data.
Setting
data
Applicable device
Internal device
File register
Link direct device
J\
Intelligent function
module device
U\G
Index register Zn Constant Others
Bit Word Bit Word
(S)
(D)
Setting data Description Set by Data type
Un
Start I/O signal of the module
(00 to FE: The 2 upper digits of an input/output signal expressed in 3-digit.)
User BIN-16 bit
(S) Head number of the devices that store control data User, System Device name
(D)
Head bit device number of the local station that turns ON for one scan upon instruction
completion.
(D)+1 also turns on if the execution completes abnormally.
System Bit
GP.PRR
G.PRR
GP.PRR
G.PRR
Un (S) (D)
Un (S) (D)
Command
[Executing
condition]
[Instruction
code]
Command