CHAPTER 17 DEDICATED INSTRUCTIONS
17
17.4 ZP.CSET (Initial Settings)
(4) Whether the CSET instruction is being executed or has been completed
normally/abnormally can be checked by the completion device (D2)
designated as a setting data.
(a) Completion device ((D2) + 0)
Turns on at the END processing of the scan where the CSET instruction is completed, and turns off at the next
END processing.
(b) Completion device ((D2) + 1)
Turns on and off depending on the completion status of the CSET instruction.
• Normal completion: Stays off and does not change.
• Abnormal completion: Turns on at the END processing of the scan where the CSET instruction is
completed, and turns off at the next END processing.
[Operation when the CSET instruction is being executed]
Scan
Sequence program
Q series C24
END
processing
END
processing
END
processing
CSET instruction
Completion device
Completion device + 1
Setting processing
Scan Scan
Instruction execution
Abnormal completion