User`s manual

377
CHAPTER 17 DEDICATED INSTRUCTIONS
17
17.3 ZP.CSET (Programmable Controller CPU Monitoring Register/Cancel)
*1 For the LJ71C24(-R2), notification function cannot be used.
*2 For the LJ71C24(-R2), use the modem function to designate the data No. for connecting when executing the constant
cycle transmission.
*3 For the LJ71C24(-R2), use this block to designate the data No. for connecting when executing the condition agreement
transmission.
(S2)+14
1st
(first block)
Monitoring head device Designate the head number of the monitoring device in this block. 0 or more
User
(S2)+15
(S2)+16 Registration points
Designate the registration points (read points) for this block.
0: Do not monitor device.
0: Do not monitor device.
For a bit device, designate the points in word units.
0, 1 or more
(S2)+17
Condition
agreement
transmission
Monitoring
condition
Designate the monitoring condition for this block.
0: No designation (at constant cycle transmission)
1 or more: Monitoring condition
Page 37,
Section 2.2.2
(2)
(S2)+18
Monitoring
condition
value
Designate the monitoring condition value for this block.
0 or more: Monitoring condition
Designate 0 for constant cycle transmission.
(S2)+19
User frame
output head
pointer
Designate the head pointer of the table designating the user
frame number for condition agreement transmission for this block.
0: No designation (at constant cycle transmission and
notification
*1
)
1 to 100: Head pointer
0, 1 to 100
(S2)+20
User frame
transmission
count
Designate the user frame transmission (output) count in condition
agreement transmission for this block.
0: No designation (at constant cycle transmission and
notification
*1
)
1 to 100: Transmission count
0, 1 to 100
(S2)+21
Modem
connection
data No.
Designate the data No. for connecting the modem function when
sending notifications in condition agreement transmission for this
block.
*3
0: No designation (at data transmission and constant cycle
transmission)
BB8H to BD5H: Data No. for connection (flash ROM)
8001H to 801FH: Data No. for connection (buffer memory)
0,
BB8H to
BD5H,
8001H to
801FH
(S2)+22 to
(S2)+102
Programmable controller CPU monitoring setting
2nd to 10th
(2nd to 10th block)
The same arrangement as the first programmable controller CPU
monitoring setting item.
(S2)+103
CPU status
monitoring setting
(Abnormal
monitoring) 11th
(11th block)
Condition
agreement
transmission
Fixed value
Designate the fixed value when the CPU status monitoring is
performed.
1
(S2)+104 0
(S2)+105 0
(S2)+106 1
(S2)+107 5
(S2)+108 1
(S2)+109
User frame
output head
pointer
Designate the head pointer of the table designating the user
frame number for condition agreement transmission for this block.
0: No designation (at constant cycle transmission and
notification
*1
)
1 to 100: Head pointer
0, 1 to 100
(S2)+110
User frame
transmission
count
Designate the user frame transmission (output) count in condition
agreement transmission for this block.
0: No designation (at constant cycle transmission and
notification
*1
)
1 to 100: Transmission count
0, 1 to 100
(S2)+111
Modem
connection
data No.
Designate the data No. for connecting the modem function when
sending notifications in condition agreement transmission for this
block.
*3
0: No designation (at data transmission and constant cycle
transmission)
BB8H to BD5H: Data No. for connection (flash ROM)
8001H to 801FH: Data No. for connection (buffer memory)
0,
BB8H to
BD5H,
8001H to
801FH
Device Item Setting data Setting range Set by