User`s manual

323
CHAPTER 13 COMMUNICATING WITH ASCII CODE (ASCII-BIN CONVERSION)
13
13.4 Example of Data Communication Using the Non Procedure Protocol
13.4 Example of Data Communication Using the Non
Procedure Protocol
This section shows examples of data communication using the non procedure protocol when the following
settings/registrations are made.
(1) Settings via GX Developer
Perform the following settings on the "Intelligent function module switch setting" screen.
(2) Settings via GX Configurator-SC
Register the following items on the "Transmission control and others system setting," "Non procedure system
setting," and "Transmission user frame No. designation system setting" screens.
For items other than those listed below, the default values are used.
Setting item Setting value Remarks
Switch 1
CH1 Transmission setting
Set according to the external device
CH1 Communication rate setting
Switch 2 CH1 Communication protocol setting 0006H Nonprocedural protocol
Switch 3
CH2 Transmission setting
0000H
Not usedCH2 Communication rate setting
Switch 4 CH2 Communication protocol setting 0000H
Switch 5 Station No. setting 0000H Station number of the Q series C24
Registration screen Setting item Setting value
"Non procedure system setting" screen
Received data count designation 0003H
Receive complete code designation 0009H
Receive user frame designation
User frame use enable/disable designation
Enable
Receive user frame designation
First frame No. designation 1st
03E8H
Receive user frame designation
First frame No. designation 2nd
03E9H
Receive user frame designation
Last frame No. designation 1st
041BH
Receive user frame designation
Last frame No. designation 2nd
041BH
Transmission user frame designation
Output head pointer designation
0001H
Transmission user frame designation Output count designation 0005H
"Transmission user frame No. designation system
setting" screen
Transmission frame No. designation 1st 43F2H
Transmission frame No. designation 2nd 43F3H
Transmission frame No. designation 3rd C001H
Transmission frame No. designation 4th 8000H
Transmission frame No. designation 5th 441BH
"Transmission control and others system setting"
screen
ASCII-BIN conversion designation Enable