User`s manual
144
3.4.5 Initialization of modem/TA (terminal adapter)
This section explains the initialization of the modem/TA connected to the Q series C24, used for communicating data
with the external device, performing notifications to pager receivers and accessing from GX Developer using the
modem function.
(1) Requirements for initialization
Perform the following setting and registration:
• The initial settings for the Q series C24 as shown in Page 134, Section 3.4.3
• The data for initialization registration shown in Page 134, Section 3.4.3, when initializing the modem/TA with
the data for initialization set by the user.
Remark
It is possible to initialize and connect at the same time by performing the connection process by designating the data for
initialization and data for connection. ( Page 148, Section 3.4.6)
(2) Registering initialization data using GX Configurator-SC (Settings on the
modem function system setting screen)
The number of the initialization data used to initialize the modem connected to the Q series C24 is registered on
the GX Configurator-SC's "Modem function system setting" screen.
The following explains the number designated by the "Initialization data number" item on the GX Configurator-
SC's "modem function system setting" screen and the related buffer memory when the initialization data number
= 0 is designated.
*1 The data for initialization registration number to be used is designated.
7D0H to 7DDH (2000 to 2013): Data registered by the OS
9C4H to 9E1H (2500 to 2529): Data registered in the Flash ROM by the user
8001H to 801FH (-32767 to -32737): Data registered to the buffer memory by the user
1) Output head pointer designation area (address: 184/344 (B8H/158H)): Designate the location of the head
position (n-th unit) in the transmission frame number designation area to which the registration number of the
data for initialization to be sent is written.
• 1: Transmitted form the first unit to 100: Transmitted from the 100th unit
Buffer memory used
The number of data for initialization used and buffer memory designated value
Name
Address (CH1/CH2)
Hexadecimal Decimal When number used = 1 When number used = 2 or more
Data number for initialization
designation
34H 52
7D0H to 801FH:
Data for initialization registration number
*1
0H
User frame being transmitted
number
B6H/156H 182/338
(Unused)
(During initialization, the data registration
number currently being sent is stored.)
CR/LF output designation B7H/157H 183/339 0 (default value)
Output head pointer
designation
B8H/158H 184/340 1 to 100 (See 1))
Output count designation B9H/159H 185/341 1 to 100 (See 2))
Transmission
frame
number
designation
First BAH/15AH 186/342
7D0H to 801FH:
Data for initialization registration number
*1
Second BBH/15BH 187/343
Hundredth 11DH/1BDH 285/445