User`s manual

117
CHAPTER 3 COMMUNICATIONS BY THE MODEM FUNCTION
3
3.3 Specifications
(4) Details of buffer memory (for the callback function)
The areas shown below are valid if the Q Series C24 uses the callback function.
(a) Callback function designation area (Address 8193 (2001H))
If communications are done by connecting to the GX Developer via a modem, specify whether the callback
function is to be used or not. Also specify the callback operation in the case that the callback function is
used.
This specification becomes valid if "Connection" is entered in the GX Developer connection designation area
(Address 54 (36H).
Show the setting value (the value stored in this area) in the GX Configurator-SC and show the corresponding
Q Series C24's callback operation. This becomes invalid if any setting values other than those shown below
are specified, and the callback function does not operate.
When the callback function is not to be used: Auto (0H)
When the callback function is to be used: Setting 1 (9H) to setting 6 (7H)
Setting 1 (9H): Auto/Callback connection (during fixed)
Setting 2 (BH): Auto/Callback connection (during designation number)
Setting 3 (FH): Auto/Callback connection (during max. designation number is 10))
Setting 4 (1H): Callback connection (during fixed)
Setting 5 (3H): Callback connection (during designation number)
Setting 6 (7H): Callback connection (during max. designation number is 10))
(b) Callback denial notification accumulated count designation area (Address 8194
(2002H))
Use 0 to FFFFH to designate the accumulated count that will be the notification timing to the QCPU when a
denial of the callback occurs during access from GX Developer after the Q series C24 has been started up.
The accumulated number of times up to the present a denial of the callback occurred (accumulated count
value in the Q series C24) after starting up can be checked in the area where the accumulated count of
denial of the callback is stored (address 8945 (22F1H)).