User`s manual

108
*1 Only the QJ71C24N (-R2/R4) are usable. (System area when using QJ71C24 (-R2))
*2 Only the Q series C24 is usable. (System area when using the L series C24)
*3 Buffer memory areas that can be used with the modem function
8199 (2007H)
For modem
function
designation-2
*3
Auto modem initialization designation
0: No auto initialization, 1: Auto initialization
0
RW
8200 (2008H)
Modem initialization time DR (DSR) signal valid/invalid
designation
0: DR signal is not ignored., 1: DR signal is ignored.
1
8201 (2009H)
Complete signal handling designation for modem function
0: Does not turn ON/OFF from X13 to X16
1: Turns ON/OFF from X13 to X16
1
8202 (200AH)
Wait time of notification
*2
0H: No waiting time
1H to FFFFH: Wait time of notification (Notification interval
time)
(Unit: s)
10
8203 (200BH) (Use prohibited) System area
8204 (200CH)
For remote
password
function
*3
Remote password mismatch notification count designation
0H: No designation
1H to FFFFH: Count for notification
0
RW
8205 (200DH)
Remote password mismatch notification accumulated count
designation
0H: No designation
1H to FFFFH: Notification accumulated number count
1
8206 (200EH)
For modem
function
designation - 3
*3
Circuit disconnect wait time (programmable controller CPU
watch use)
0000H to FFFH: Wait time (Unit: s)
0RW
8207 (200FH) (Use prohibited) System area
8449 to 8458 (2101H to 210AH)
For callback
function
*3
Data No. for callback designation 1 to 10
0BB8H to 0BD5H, 8001H to 801FH: Data number for callback
0RW
8944 (22F0H)
For callback
function
*3
Callback permit accumulated count
0 or more: Accumulated count
0RW
8945 (22F1H)
Callback denial accumulated count
0 or more: Accumulated count
8946 (22F2H)
Auto (callback) connection permit accumulated count
0 or more: Accumulated count
8947 (22F3H)
Auto (callback) connection denial accumulated count
0 or more: Accumulated count
8948 (22F4H)
Accumulated count of callback receive procedure cancel
0 or more: Accumulated count
8949 to 8954 (22F5H to 22FAH) (Use prohibited) System area
8955 (22FBH)
For remote
password
function
*3
Accumulated count of unlock process normal completion
0 or greater: Accumulated count of normal completion
0RW
8956 (22FCH)
Accumulated count of unlock process abnormal completion
0 or greater: Accumulated count of abnormal completion
8957 to 8958 (22FDH to 22FEH) (Use prohibited) System area
8959 (22FFH)
For remote
password
function
*3
Accumulated count of lock process based on circuit line
disconnection
0 or greater: Accumulated count of lock process based on
circuit line disconnection
0RW
9216 (2400H) (Use prohibited) System area
9728 to 16383 (2600H to 3FFFH)
For user
*1
User free area 2 (6656 words)
(Communication data monitoring function default buffer)
Application is determined by the user.
0RW
Address Dec. (Hex.)
Application Name
Default
value
Correspondence
protocol
CH1 CH2 MC Non Bi