User`s manual
106
57 to 127 (39H to 7FH) (Use prohibited) System area
128 (80H)
For programmable
controller CPU
information clear
*1
Programmable controller CPU information clear request
0000H: No request
4C43H: Requested
129 to 143 (81H to 8FH) (Use prohibited) System area
144 (90H) 304 (130H)
For specifying
mode switching
Switching mode number designation
0RW
145 (91H) 305 (131H) Transmission specification designation after switching
146 (92H) 306 (132H)
Signal setting
*1
RS and DTR signal status designation 0005H RW
183 (B7H) 343 (157H)
Transmission user
frame
CR/LF output designation
0 RW
184 (B8H) 344 (158H) Output head pointer designation
185 (B9H) 345 (159H) Output count designation
186 to 285
(BAH to 11DH)
346 to 445
(15AH to 1BDH)
Transmission frame No. designation (A maximum of 100
frames can be designated.)
544 (220H) Flash ROM Flash ROM system parameters write result 0 RW
545 (221H)
For modem
function
confirmation
*3
Modem function error code
0: Normal completion
1 or more: Abnormal completion (error code)
0RW
546 (222H)
Modem function sequence status
0: Idle status
1: Waiting for initialization
2: Initializing modem
3: Standby in progress
4: Checking password
5: Communication in progress
6: Notification in progress (Valid for Q series C24 only, not for
L series C24.)
7: Modem disconnection
8: Callback Request reception waiting
9: Callback Modem disconnect waiting
10: Callback Delay time waiting
11: Callback Reconnecting
12: Callback Rechecking password
0
R
547 (223H)
Number of data registrations for connection
0: No registration, 1 or more: Number of registration
The values
vary
depending
on the
registration
status
548 to 549 (224H to 225H)
Data registration status for connection (for conformation of
registration No.)
0: No registration, 1: Registered
• Bits for registration number are 0 (ON)/1 (OFF)
Registration number BB8H (3000): Address 224H (b0) to
Registration number BD5H (3029): Address 225H (b13)
550 (226H)
Number of data registrations for initialization
0: No registration, 1 to 30: The number of registrations
551 to 552 (227H to 228H)
Data registration status for initialization
0: No registration, 1: Registered
• Bits for registration number are 0 (ON)/1 (OFF)
Registration number 9C4H (2500): Address 227H (b0) to
Registration number 9E1H (2529): Address 228H (b13)
Address Dec. (Hex.)
Application Name
Default
value
Correspondence
protocol
CH1 CH2 MC Non Bi