(1) Buffer memory list
Address Dec. (Hex.)
Application Name
Default
value
Correspondence
protocol
CH1 CH2 MC Non Bi
0 (0H)
For LED and
communication
error clear
Communication error clear request for CH1 and to turn LED
off
0RW
1 (1H)
Communication error clear request for CH2 and to turn LED
off
2 (2H)
For Flash ROM
access
Register/read/delete directions
0RW
3 (3H) Frame No. direction
4 (4H) Register/read/delete result storage
5 (5H) Number of data bytes registration designation
6 to 45 (6H to 2DH) User frame
46 (2EH)
For modem
functions
designation-1
*3
Modem connection channel directions
0: None, 1: CH1, 2: CH2
0
RW
47 (2FH)
Notification execution designation
*2
0: Does not execute, 1: Execute
48 (30H)
Number of connection retries designation
1 to 5: Number of retries
3
49 (31H)
Connection retry interval designation
90 to 300: Connection retry interval (unit: s)
180
50 (32H)
Initialization/connection timeout designation
1 to 60: Time out (unit: s)
60
51 (33H)
Number of initialization retries designation
1 to 5: Number of retries
3
52 (34H)
Data number for initialization designation
0H: Sends initialization data designated by the transmission
user frame designation area
7D0H to 801FH: Data No. for initialization
7D0H
(2000)
53 (35H)
Data number for connection designation
BB8H to 801FH: Data number for connection
0
54 (36H)
[When using Q series C24]
GX Developer connection designation
0: Does not connect, 1: Connects
[When using L series C24]
MELSOFT connection designation
0: Does not connect, 1: Connects
55 (37H)
No-communication interval time designation
0: Waits infinitely
1 to 120: Non-communication interval time (Line disconnection
wait time)
(Unit: min)
30
56 (38H)
RS/CS control yes/no designation
0: Does not control, 1: Controls
1