User`s manual
8
3. SPECIFICATIONS
3.1 General Specifications
This section describes general specifications of the QA6ADP.
*1 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from
fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500
V.
Item Specifications
Operating ambient
temperature
Température
ambiante de
fonctionnement
0 to 55 °C
0 à 55 °C
Storage ambient
temperature
-20 to 75 °C
Operating ambient
humidity
10 to 90 % RH, No-condensing
Storage ambient
humidity
10 to 90 % RH, No-condensing
Vibration
resistance
Conforming
to
JIS B 3502,
IEC 61131-2
Frequency
Accelera
-tion
Amplitude
Sweep
count
Under
intermittent
vibration
10 to 57 Hz 0.075 mm
10 times
each in
X, Y, Z
directions
57 to 150 Hz 9.8 m/s
2
Under
continuous
vibration
10 to 57 Hz
00.35 mm
(0.001 in.)
57 to 150 Hz 4.9 m/s
2
Shock resistance
Conforming to JIS B 3502, IEC 61131-2
(147 m/s
2
, 3 times in each of 3 directions XYZ)
Operation
ambiance
No corrosive gasses
Operating
elevation *3
0 to 2000 m
Installation location Control panel
Overvoltage
category *1
II max.
Pollution degree *2 2 max.
Equipment
category
Class I