QA6ADP QA Conversion Adapter Module User's Manual QA6ADP Thank you for purchasing the Mitsubishi programmable controller MELSEC-Q series. Prior to use, please read this and relevant manuals thorougly to fully understand the product.
CONDITIONS OF USE FOR THE PRODUCT (1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions; i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident; and ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are required. For details, please contact the Mitsubishi representative in your region.
REVISIONS * The manual number is noted at the lower right of the top cover. Print Date Aug., 2007 Mar., 2008 *Manual Number IB(NA)-0800402-A IB(NA)-0800402-B Mar., 2010 IB(NA)-0800402-C Apr., 2010 IB(NA)-0800402-D Mar., 2011 IB(NA)-0800402-E Oct., 2011 IB(NA)-0800402-F May, 2014 IB(NA)-0800402-G Revision First printing Partial correction Section 2.2, 6.1 Partial correction Section 2.2 Addition CONDITIONS OF USE FOR THE PRODUCT Partial correction Back cover Partial correction Section6.
CONTENTS 1. OVERVIEW .................................................................................................... 1 1.1 Overview................................................................................................... 1 1.2 Included Parts........................................................................................... 2 2. SYSTEM CONFIGURATION ......................................................................... 3 2.1 System Configuration .....................................
1. OVERVIEW 1.1 Overview This user’s manual describes the specifications, configuration device, part names and setting, and implementation and installation of the QA6ADP QA conversion adapter module. For contents that are not described in this manual such as safety precautions, EMC and low voltage directives, or error code list, refer to QCPU User’s Manual (Hardware Design, Maintenance and Inspection) (SH-080483).
1.2 Included Parts This section describes parts included with this module.
2. SYSTEM CONFIGURATION 2.1 System Configuration This section describes the system configuration and restrictions when the QA6ADP is used. (1) The QA6ADP+A5B/A6B is only applicable for the following CPU modules. • High Performance model QCPU • Universal model QCPU whose serial number (first five digits) is "13102" or later (2) Mount the Q5B/Q6B, QA6B, and QA6ADP+A5B/A6B in order from the nearest position of the main base unit. The QA6ADP cannot be used in combination with the QA1S5B or QA1S6B.
(8) The bus connection with GOT is not available for the QA6ADP+A5B/A6B. Power supply [Extension stage number setting] Stage number setting connector CPU module 0 1 2 3 4 5 6 7 .........Q38B 8 9 10 11 12 13 14 15 Power supply 1 Main base unit ..............Q68B Q series compatible extension base unit (The Q5 B/Q6 B is connected to the main base unit or the Q5 B/Q6 B.) Power supply 16 17 18 19 20 21 22 23 2 ...
2.2 Configuration Device List (1) Extension base unit mountable on the QA6ADP The following shows extension base units that can be mounted on the QA6ADP.
Product name High-speed counter module A/D converter module D/A converter module Temperature-digital converter module Interrupt module Positioning module A-A1S module conversion adapter MELSECNET/MINI-S3 master module Intelligent communication module PC fault detection module MELSEC-I/OLINK module B/NET interface module Blank cover Dummy module AD61, A68AD, A616AD A62DA, A68DAI-S1, A68RD3, A68RD4N, A60MXR, A60MXTN AI61, AD70, AD71S1, AD72 AD75M1, AD75P1-S3, A1ADP-XY, Model AD61S1 A68AD-S2, A68ADN,
*1 *2 The dedicated instructions used in the QnA/A series program cannot be used in the QCPU. Replace the dedicated instructions with the FROM/TO instructions. There is restriction on the number of mountable modules. Product name Intelligent communication module Interrupt module *3 *4 *5 *6 Model AD51, AD51-S3, AD51H, AI61, AD51E, AD51E-S3, AD51H-S3 AI61-S1 No.
3. SPECIFICATIONS 3.1 General Specifications This section describes general specifications of the QA6ADP. Item Operating ambient temperature Température ambiante de fonctionnement Storage ambient temperature Operating ambient humidity Storage ambient humidity Specifications 0 to 55 °C 0 à 55 °C -20 to 75 °C 10 to 90 % RH, No-condensing 10 to 90 % RH, No-condensing Accelera Amplitude -tion 10 to 57 Hz 0.
*2 *3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected occasionally. Do not use or store the programmable controller in the environment when the pressure is higher than the atmospheric pressure at sea level. Otherwise, malfunction may result.
4. PART NAMES AND SETTING 4.1 Part Names This section describes part names of the QA6ADP . 9) 8) 3) 1) 7) 6) 4) 2) 5) No. 1) 2) 3) 4) 5) 6) 7) 8) 9) Name Extension cable connector Stage number setting connector Adapter module mounting screw (M3 screw) 3) Application Connector for sending/receiving signals to the main base unit or the other extension base unit and connecting an extension cable. Connector for setting the number of extension stages.
4.2 Extension Stage Number Setting Set the number of extension stages to both the QA6ADP and the extension base unit. The same stage number should be set to both the stage number setting connector of the extension base unit and that of the QA6ADP. POINT Set any number of 1 to 7 which matches to the number of extension stages for the stage number setting connector setting.
5. MOUNTING AND INSTALLATION 5.1 Mounting/Removal of QA6ADP (1) Mounting of the QA6ADP The following shows procedures for mounting the QA6ADP on the extension base unit. A) Disconnect the A series extension cable from the extension base unit. Remove a base cover from the extension base unit. Set the stage number setting connector of the extension base unit. Set the stage number setting connector of the QA6ADP.
(2) Removal of the QA6ADP The following shows procedures for removing the QA6ADP from the extension base unit. Disconnect an extension cable form the QA6ADP. Board fixing screw Remove the adapter module mounting screws of the QA6ADP at two parts (top and bottom). Remove the QA6ADP main body from the extension base unit. Remove a board fixing screw and an adapter module mounting bracket of the QA6ADP.
5.2 Connection/Disconnection of Extension Cable (1) Precautions for handling an extension cable • Do not step on an extension cable. • When laying an extension cable, the minimum bend radius of the cable should be 55 mm (2.17 inch) or more. If it is less than 55 mm (2.17 inch), malfunction may occur due to characteristic deterioration, wire break etc. • When connecting or disconnecting an extension cable, do not hold ferrite cores mounted at both ends of the cable.
POINT When connecting the base unit of the previous stage and the QA6ADP with an extension cable, be sure to connect the OUT side connector of the base unit of the previous stage and the IN side connector of the QA6ADP. If an extension cable is connected in the wrong way (ININ, OUTOUT or INOUT), the system will not operate normally. • To connect an extension cable to the QA6ADP, remove a sticker on the IN side connector.
• Hold the connector part of an extension cable when connecting the extension cable to the QA6ADP. Extension base unit QA6ADP Connector Extension cable • Make sure to tighten fixing screws of the extension cable connector after connecting the extension cable. (Tightening torque: 0.
6. PRECAUTION FOR USING QA6ADP 6.1 Current Consumption of QA6ADP Since 5VDC is supplied to the QA6ADP from the power supply module of the main base unit, take the current consumption of the QA6ADP into consideration when selecting the power supply module for the main base unit.
In case of the above system, use the QA6ADP when the current consumption of the power supply module mounted on the main base unit meets the following formula. [Calculating formula] I > I0 + I2 + I3 + IA 3 6.2 Voltage Drop of Extension Cable Since 5VDC is supplied to the QA6ADP from the power supply module mounted on the main base unit, the voltage drop will be caused in the extension cable. If the specified voltage (4.
*1 Current consumption at each extension base unit is as follows: First extension base unit: None Second extension base unit: IA+I2 Third extension base unit: IA Since the first extension base unit and the third extension base unit are supplied from the power supply module on each extension base unit, the values are not included above. Since the current consumptions I1 to I3 vary depending on modules to be mounted, refer to the manual for the module to be mounted.
7. COMPATIBLE MODELS LIST This chapter describes external dimensions of the QA6ADP. A series extension base unit that you have already had QA6ADP QA conversion adapter module 2 6-M4 screw (for mounting module) 4-f 6mounting hole (M5 mounting screw) Handle I/O I/O I/O I/O I/O 200 (7.87) 130 (5.11) POWER 9 (0.35) 74 (2.91) 73.5 (2.89) Power supply module, Extension cable 250 (9.84) Power supply module Extension cable 121 (4.76) 172 (6.
WARRANTY Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties. Country/Region Sales office/Tel Country/Region Sales office/Tel USA Mitsubishi Electric Automation lnc.