3 - 15 3 - 15
MELSEC-Q
3 SPECIFICATIONS
3.3.2 Details of I/O signals
I/O signals for the D/A converter module are explained in detail below.
(1) Input signals
Device No. Signal name Description
X0 Module READY
(1) When the PLC CPU is powered on or reset, this signal turns on once the preparation
for D/A conversion has been completed, and D/A conversion processing is then
performed.
(2) When the Module READY (X0) signal is off, D/A conversion processing is not
performed. Module READY (X0) turns off in the following situations:
• During offset/gain setting mode
When the D/A converter module has a watchdog timer error
X8
High resolution
mode status flag
(1) This turns ON when in high resolution mode.
X9
Operating
condition setting
completed flag
(1) This is used as an interlock condition for turning the operating condition setting
request (Y9) ON/OFF when the setting for D/A conversion enable/disable (buffer
memory address 0: Un\G0) is changed.
(2) Under the following conditions, the operating condition setting completed flag (X9)
turns OFF.
When Module READY (X0) is OFF
When operating condition setting request (Y9) is ON
Performed by the D/A converter module
Performed by the sequence program
Module READY (X0)
Operating condition
setting completed flag (X9)
Operating condition
setting request (Y9)