7 - 17 7 - 17
MELSEC-Q
7 ONLINE MODULE CHANGE
(4) Operation check
(a) To make an operation check, click the [Cancel] button to cancel control
resumption.
(b) Click the [OK] button to leave the "Online module change" mode.
(c) Click the [Close] button to close the System monitor screen.
(d) Set digital values to the digital values (buffer memory addresses 1 to 8:
Un\G1 to 8) and turn Operating condition setting request (Y9) from OFF to
ON. Turn ON the output enable/disable flag (Y1 to Y8) of the used channel
to check whether proper conversion has been made or not.
(Be careful since analog outputs are provided actually.)