User`s manual
5 - 23 5 - 23
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-DA)
5.6.4 Pass data
Perform operation in the following sequence to save/restore the user range.
(1) Switch to the pass data screen
Perform the operation in Section 5.6.1 to display the Pass data screen.
(2) User range saving
(a) Set the user range to be used in the Setting value field of CH Pass data
classification setting, and click the Execute test
button.
When the user range setting is completed, the set user range is displayed in
the Current value field of CH
Pass data classification setting.
(b) Change the Setting value field of Pass data read request to "Request", and
click the Execute test
button.
When read is completed, the values are displayed in the Current value fields
of CH
Industrial shipment settings offset/gain values/CH User range
settings offset/gain values.
(c) Compare the values with those in the range reference table, and record
them if they are correct.
Refer to Section 7.4 for the range reference table.