User`s manual

5 - 13 5 - 13
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-DA)
5.4 Initial Setting
[Purpose of setting]
Set the following items in the initial setting parameters.
• D/A conversion enable/disable setting
• Rate control enable/disable setting
• Increase/decrease digital limit values
• Disconnection detection setting
• Warning output setting
Warning output upper limit value/lower limit value
This initial setting makes sequence program setting unnecessary.
[Startup procedure]
"Start I/O No. " "Module type" "Module model name" Initial setting
[Setting screen]
[Explanation of items]
(1) Setting contents
Set the D/A conversion enable/disable setting, rate control enable/disable setting
and others for each channel.
(2) Explanation of command buttons
Make text file
Outputs the screen display in text file format.
End setup
Confirms the setting data and ends the operation.
Cancel
Cancels the setting data and ends the operation.
POINT
Initial settings are stored in the intelligent function module parameters. After being
written to the CPU module, the initial setting is made effective by either (1) or (2).
(1) Cycle the RUN/STOP switch of the CPU module: STOP
RUN STOP
RUN.
(2) With the RUN/STOP switch set to RUN, turn off and then on the power or reset
the CPU module.
When using a sequencer program to write the initial settings, when the CPU is
switched from STOP to RUN the initial settings will be written, So ensures that
programming is carried out to re-execute the initial settings.