User`s manual
5 - 1 5 - 1
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-DA)
5 UTILITY PACKAGE (GX Configurator-DA)
5.1 Utility Package Functions
Table 5.1 shows an overview of the utility package functions.
Table 5.1 Utility package (GX Configurator-DA) function list
Item Description Reference section
Initial setting
1
(1) Set the following items that require initial setting.
• D/A conversion enable/disable setting
• Rate control enable/disable setting
• Increase/decrease digital limit values
• Disconnection detection setting
• Warning output setting
• Warning output upper limit value/lower limit value
(2) The data for which initial setting has been completed is registered in
the parameters for the PLC CPU, and automatically written to the
Q62DA-FG when the PLC CPU changes to RUN status.
Section 5.4
Automatic refresh setting
1
(1) Sets automatic refresh for the Q62DA-FG buffer memory.
(2) The buffer memory that was set for automatic refresh is
automatically read and written to the specified device when the
END command for the PLC CPU is executed.
Section 5.5
Monitor/Test
(1) Monitor/Test
The buffer memory and I/O signals for the Q62DA-FG are
monitored and tested.
(2) Operating condition setting
Changes the D/A conversion enable/disable during operation.
(3) Offset/gain setting
When setting the offset/gain to a value selected by the user (when
the analog output range setting is user range setting), the offset and
gain can be easily set while viewing the screen.
(4) Pass data
The pass data (pass data classification setting, industrial shipment
settings offset/gain values, user range settings offset/gain values)
can be monitored and set.
Section 5.6
FB conversion
Generates FB automatically from the intelligent function module
parameter (initial setting/auto refresh setting).
Section 5.7
POINT
1 If initial setting and automatic refresh setting are performed, the intelligent
function module parameters require a maximum of 24 bytes per module.
5