4 SETUP AND PROCEDURES BEFORE OPERATION
4.4 Wiring
The wiring precautions and examples of module connection are provided below.
4.4.1 Wiring precautions
In order to optimize the functions of the Q62DA-FG and ensure system reliability,
external wiring that is protected from noise is required.
Please observe the following precautions for external wiring:
(1) Use separate cables for the alternating-current control circuit and the external
output signals and external supply power of the Q62DA-FG in order to avoid AC
surges and induction effects.
(2) Do not mount the cables close to or bundle them with the main circuit line, a high-
voltage cable or a load cable from other than the PLC. This may increase the
effects of noise, surges and induction.
(3) Perform a one-point grounding for shielded lines and the shields of sealed cables.
(4) A solderless terminal with insulating sleeve cannot be used for the terminal block.
Covering the cable- connection portion of the solderless terminal with a marked
tube or an insulation tube is recommended.