User`s manual
3 - 25 3 - 25
MELSEC-Q
3 SPECIFICATIONS
3.4.9 Offset/gain range setting (buffer memory address 25: Un\G25)
(1) This area is used to change the output range in the offset/gain setting mode.
Turning ON the channel change request (YB) changes the output range into the
set one.
If any value outside the setting range is set, an error occurs and the corresponding
error code (buffer memory address 19: Un\G19) is stored.
Output range Set value
User range setting 1 000F
H
User range setting 2 000E
H
User range setting 3 000D
H
(2) The channel change request (YB) must be turned ON/OFF to validate the
offset/gain range setting. (Refer to Section 3.3.2.)
(3) Refer to Section 4.6 for details of offset/gain setting.
3.4.10 CH output monitor value (buffer memory addresses 38, 39: Un\G38, Un\G39)
(1) The analog value being output is always reconverted into a digital value within the
Q62DA-FG and the result is stored. (Refer to Section 3.2.3.)
Output range setting Output monitor value
0 to 20 mA
4 to 20 mA
User range setting 1
1 to 5 V
0 to 5 V
0 to 12000
–10 to 10 V –16000 to 16000
User range setting 2 –12000 to 12000
User range setting 3 0 to 12000
(2) Turning ON the operating condition setting request (Y9) clears the output monitor
value.
3.4.11 Rate control enable/disable setting (buffer memory address 46: Un\G46)
(1) Set whether to enable or disable the rate control on each channel. (Refer to
Section 3.2.5.)
(2) The operating condition setting request (Y9) must be turned ON/OFF to validate
the rate control enable/disable setting. (Refer to Section 3.3.2.)
(3) The default setting is all-channel rate control disable.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1: Rate control disable
0: Rate control enable
b2 to b15 information is fixed at 0.
0 CH2 CH10000000000000Un\G46