3 SPECIFICATIONS
3.4.2 D/A conversion enable/disable setting (buffer memory address 0: Un\G0)
(1) Set whether D/A conversion is enabled or disabled for each channel.
(2) It is necessary to set the operating condition setting request (Y9) to ON/OFF to
validate the D/A conversion enable/disable setting. (See Section 3.3.2.)
(3) By default, all channels are set to D/A conversion disabled.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH
2
CH
1
1: D/A conversion disabled
0: D/A conversion enabled
Un\G0
0000000
b2 to b15 information is fixed at 0.
0000000
3.4.3 CH digital values (buffer memory addresses 1, 2: Un\G1, Un\G2)
(1) This area is used to write digital values for performing D/A conversion from the
PLC CPU as 16-bit signed binary code.
(2) Settings for digital values to be D/A converted when a value outside the valid
digital value setting range is used are listed in Table 3.7.
When a value outside the valid range is written, a check code is stored in the set
value check codes (Un\G11, Un\G12).
Table 3.7 Output range settings and valid range
Output range setting Valid range (practical range)
Digital value that is set when a value outside
the valid range is written
0: 4 to 20 mA
1: 0 to 20 mA
2: 1 to 5 V
3: 0 to 5 V
0 to 12287
(Practical range: 0 to 12000)
12288 or larger: 12287
–1 or smaller: 0
4: –10 to 10 V
-16384 to 16383
(Practical range: -16000 to 16000)
16384 or larger: 16383
–16385 or smaller: 16384
D: User range setting3
E: User range setting2
F: User range setting1
-12288 to 12287
(Practical range: -12000 to 12000)
12288 or larger: 12287
–12289 or smaller: –12288