3 SPECIFICATIONS
3.2.6 Disconnection detection function
(1) When the analog output value falls to or below 1ma accuracy (1.0%) in the
output range of 4 to 20mA or user range setting 1, the disconnection detection flag
(buffer memory address 49: Un\G49) and disconnection detection signal (XD) turn
ON and disconnection is detected.
Disconnection is detected only on the channel set for D/A conversion enable and
D/A output enable.
(2) The disconnection detection flag (buffer memory address 49: Un\G49) and
disconnection detection signal (XD) turn OFF when the operating condition setting
request (Y9) or disconnection detection clear request (YD) turns ON.
(3) For the disconnection detection function, the disconnection detection/warning
output setting (buffer memory address 47: Un\G47) allows enable/disable of the
disconnection detection to be specified for each channel. To enable the
disconnection detection, write "0" to the bit position corresponding to the channel
number and turn ON the operating condition setting request (Y9). The default is
all-channel disable.
20
0
1
Output monitor value (mA)
Disconnection detection
signal (XD)
OFF ON
Disconnection detection
clear request (YD)
OFF
ON
Disconnection detection flag
(buffer memory address 49
: Un\G49)
OFF ON
OFF
OFF
Disconnection assumed range
10
POINT
If the analog output value is 1mA or less at the user range setting 1, disconnection
is detected if disconnection has not occurred actually.
When the analog output value is 1mA or less, disable the disconnection detection
function.