User`s manual
3 - 2 3 - 2
MELSEC-Q
3 SPECIFICATIONS
1: Accuracy of offset/gain setting at ambient temperature
Q62DA-FG needs to be powered on 30 minutes prior to operation for compliance to the specification (accuracy).
2: Accuracy per temperature change of 1 °C
Example: Accuracy when temperature changes from 25 to 30 °C
0.1% (Reference accuracy) + 0.008%/ °C (temperature coefficient)
5 °C (temperature change difference) = 0.14%
3: The following indicates the external load resistance when output current is 20mA or more.
22mA
20mA
Output
current
External load resistance
500
500
REMARK
See the user's manual for the CPU module being used for the general specifications
for the Q62DA-FG.
3.1.2 I/O conversion characteristics
I/O conversion characteristics are used for converting the digital value written from the
PLC CPU to an analog output value (voltage or current output), and represented by
inclined straight lines when offset and gain values are included.
Offset value
The offset value becomes the analog output value (voltage or current) when the digital
input value set from the PLC CPU is 0.
Gain value
The gain value denotes the analog output value (voltage or current) when the digital
input value set from the PLC CPU is
12000 (when 1 to 5V, 0 to 5V, 4 to 20 mA, 0 to 20 mA or the user range setting1 to 3 is
selected),
16000 (when -10 to 10V is selected).
3