User`s manual

App - 5 App - 5
MELSEC-Q
APPENDIX
Control data
1
(2/2)
Device Item Set data Setting range Set by
(S) + 10
CH2 Industrial shipment settings
offset value (used for monitor output)
——System
(S) + 11
CH2 Industrial shipment settings gain
value (used for monitor output)
——System
(S) + 12
CH1 User range settings offset value
(used for D/A)
——System
(S) + 13
CH1 User range settings gain value
(used for D/A)
——System
(S) + 14
CH2 User range settings offset value
(used for D/A)
——System
(S) + 15
CH2 User range settings gain value
(used for D/A)
——System
(S) + 16
CH1 User range settings offset value
(used for monitor output)
——System
(S) + 17
CH1 User range settings gain value
(used for monitor output)
——System
(S) + 18
CH2 User range settings offset value
(used for monitor output)
——System
(S) + 19
CH2 User range settings gain value
(used for monitor output)
——System
1 Set only the pass data classification setting (S)+2. If data is written to the area set by the system, the offset/gain values
will not be read properly.
(1) Functions
(a) Reads the offset/gain values of the user range setting of the Q62DA-FG to
the CPU.
(b) There are two types of interlock signals for the G.OGLOAD instruction: the
completion device (D) and the status display device at completion (D) + 1.
1) Completion device
Turns ON in the END processing of the scan where the G.OGLOAD
instruction is completed, and turns OFF in the next END processing.
2) Status display device at completion
Turns ON and OFF depending on the completion status of the
G.OGLOAD instruction.
Normal completion : Stays OFF and does not change.
Abnormal completion: Turns ON in the END processing of the scan
where the G.OGLOAD instruction is completed,
and turns OFF in the next END processing.
Sequence program
END processing
G.OGLOAD instruction
ON
OFF
Completion device (D)
OFF
Status display device
at completion (D)+1
OFF
ON
ON Abnormal
completion
Normal completion
1 scan
Execution completion of
the G.OGLOAD instruction
END processing END processing END processing