User`s manual
7 - 16 7 - 16
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.4 When user range setting is used and initial setting was made with GX Configurator-DA
(other system is unavailable)
(1) Conversion disable
(a) On the Operating condition setting screen of GX Configurator-DA, set
"Disable" in the Setting value field of CH
D/A conversion enable/disable
setting, and click the [Execute test] button.
(b) After making sure that the indication in the Current value field of CH D/A
conversion enable/disable setting is "Disable", change the Setting value
field of Operating condition setting request to "Setting request", and click
the [Execute test] button to stop conversion.
Confirm that conversion has stopped with the actual analog output value.