User`s manual

7 - 8 7 - 8
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.2 When industrial shipment setting is used and initial setting was made with sequence
program
(1) Conversion disable
(a) Set D/A Conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn Operating condition
setting request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the actual analog output
value, turn OFF Operating condition setting request (Y9).
(2) Dismounting of module
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" screen.