Specifications

4 - 5
4.3 Measuring Timer
Project name QB-3
Program name MAIN
K30
Timer setting value (time limit: 3.0sec.)
T0
Y70
Y71
X5
T0
T0
0
5
7
*: OUT T is a 4-step instruction.
[Timing chart]
Contact X5
Coil T0
Normally open contact T0,
coil Y70
Normally closed contact 0b,
coil Y71
3.0sec.
The timer contact
operates delaying by a set
time after the coil is
energized. (On delay
timer)
The timer setting range is
from K1 to K32767.
Low-speed (100ms) timer
0.1 to 3276.7sec.
High-speed (10ms) timer
0.01 to 327.67sec.
When the timer setting
value is set to 0, it turns on
(time-out) by the execution
of the instruction.
• The following four types of timer are available.
Type Timer No. (default)
Low-speed
timer·············
Counts time in
units of 100ms.
High-speed
timer·············
Counts time in
units of 10ms.
Default
T0 to T2047 (2048)
Low-speed
retentive
timer·············
Accumulates
time in units of
100ms.
High-speed
retentive
timer·············
Accumulates
time in units of
10ms.
Default: 0
The value can be
changed using the
parameter.
Change the output
instruction (OUT) to
OUTH to select the
high-speed timer or
high-speed retentive timer.
To use the retentive timer,
set the device points for
the retentive timer in the
device setting of the PLC
parameter.
Refer to section 6.4 for explanation on the retentive timers.