Indoor Service Manual
Table Of Contents
- Cover
- Contents
- 1. SAFETY PRECAUTION
- 2. PART NAMES AND FUNCTIONS
- 3. SPECIFICATION
- 4. FAN PERFORMANCE AND CORRECTED AIR FLOW
- 5. SOUND PRESSURE LEVELS
- 6. OUTLINES & DIMENSIONS
- 7. WIRING DIAGRAM
- 8. REFRIGERANT SYSTEM DIAGRAM
- 9. HEATER CONTROL
- 10. HUMIDIFIER CONTROL
- 11. ERV (ENERGY RECOVERY VENTILATION) CONTROL
- 12. TROUBLESHOOTING
- 12-1. Cautions on troubleshooting
- 12-2. Self-check function
- 12-3. Self-diagnosis action table
- 12-4. Troubleshooting by inferior phenomena
- 12-5. Test point diagram
- 12-6. Trouble criterion of main parts
- 12-7. Thermistor
- 12-8. DC Fan motor (FAN MOTOR/INDOOR CONTROLLER BOARD)
- 12-9. Functions of dip switch and jumper wire
- 13. DISASSEMBLY PROCEDURE
- Back Cover
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
CND Power supply voltage (208 - 230VAC)
CNMF Fan motor output
1 - 4: 310 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
CNXA1
Connect to the indoor controller board
CNXB1
Connect to the indoor controller board
CNXC1
Connect to the indoor controller board
CNXA2
Connect to the indoor power board
CNXB2
Connect to the indoor power board
CNXC2
Connect to the indoor power board
(*1)
V
FG
Voltage on the (-) side of PC51 and
C25
(Same with the voltage between 7 (+)
and 4 (-) of CNMF)
V
CC
Voltage between the C25 pins 15
VDC
(Same with the voltage between 5 (+)
and 4 (-) of CNMF)
V
sp
Voltage between the C53 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in operation)
(Same with the voltage between 6 (+)
and 4 (-) of CNMF)
CND
CNXB1 CNXC1 CNXA1 CNMF
PC51
(*1)
C25
(*1)
C53
(*1)
36
12-5. Test point diagram
12-5-1. Power supply board
PVA-A12AA7 PVA-A30AA7
PVA-A18AA7 PVA-A36AA7
PVA-A24AA7 PVA-A42AA7