Specs

Model Number
Indoor Unit PVA-A30AA7
Outdoor Unit
PUY-A30NHA7
PUY-A30NHA7-BS
Cooling
1
Maximum Capacity Btu/h 30,000
Rated Capacity Btu/h 30,000
Minimum Capacity Btu/h 10,000
Maximum Power Input W 3,000
Rated Power Input W 3,000
Moisture Removal Pints/h 7.0
Sensible Heat Factor 0.74
Power Factor % 93.20
Efficiency
SEER 19.00
EER
1
10.00
Electrical
Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz
Guaranteed Voltage Range V AC 198 – 253
Voltage: Indoor - Outdoor, S1-S2 V AC 208 / 230
Voltage: Indoor - Outdoor, S2-S3 V DC 24
Voltage: Indoor - Remote controller V DC 12
Recommended Fuse/Breaker Size A 25
Recommended Wire Size (Indoor - Outdoor) AWG 14
Indoor Unit
MCA A 4.13
MOCP A 15.00
Fan Motor Full Load Amperage A 3.30
Fan Motor Output W 244
Airflow Rate, Dry CFM 613-744-875
Airflow Rate, Wet CFM n/a
External Static Pressure in.WG 0.30-0.50-0.80
Sound Pressure Level dB(A) 30-34-38
Drain Pipe Size In. (mm) 3/4 FPT (19.05)
Condensate Lift Mechanism, Max. Distance In. (mm) n/a
Heat Exchanger Type Plate fin coil
External Finish Color Galvanized steel cabinet-Powder coated
Slate Gray
Unit Dimensions
W: In. (mm) 21 (534)
D: In. (mm) 21-5/8 (548)
H: In. (mm) 54-1/4 (1378)
Unit Weight Lbs. (kg) 141 (64)
Indoor Unit Operating
Temperature Range
Cooling Intake Air Temp (Maximum / Minimum) °F 90 DB, 73 WB / 66 DB, 59 WB
Outdoor Unit
MCA A 19
MOCP A 26
Fan Motor Full Load Amperage A 0.40
SPECIFICATIONS: PVA-A30AA7 & PUY-A30NHA7(-BS)
Specifications are subject to change without notice. © 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.