PVA Installation Manual
Table Of Contents
- PVA-A12, 18, 24, 30, 36, 42 AA7
- Contents
- 1. Dimensions
- 2. Inspect shipment
- 3. Safety precautions
- 4. Indoor unit accessories
- 5. Selecting an installation site
- 6. Combining indoor units with outdoor units
- 7. Installing the unit
- 8. Duct connection
- 9. Mount positions
- 10. Air filter
- 11. Refrigerant piping work
- 12. Drain connections
- 13. Electrical wiring
- 14. Test run
- Table des matières
- 1. Dimensions
- 2. Vérification de la livraison
- 3. Consignes de sécurité
- 4. Accessoires de l’appareil intérieur
- 5. Sélection de l’emplacement d’installation
- 6. Combinaison des appareils intérieurs avec des appareils extérieurs
- 7. Installation de l’appareil
- 8. Raccordement des conduits
- 9. Positions de montage
- 10. Filtre à air
- 11. Mise en place des tuyaux de réfrigérant
- 12. Raccords d’évacuation
- 13. Câblage électrique
- 14. Essai de fonctionnement
- Back Cover
23
13.3. Condensate overow safety switch connection
(CN4F)
The circuit board is equipped with a connection to attach a
condensate safety oat switch. The switch should be a normally
closed low voltage rated switch. The switch should be installed in a
location that it can sense a drain blockage causing a rise in water
level. This resulting rise in level will cause it to open. The switch
location is to be determined by the installing contractor. When the
switch opens, it will cause the LEV to close, stopping the cooling
operation. The fan will continue to run and a fault code will be shown
at the controller. Correcting the problem and closing the switch will
be required before normal operation can resume.
See installation below:
13.4. Changing blower external static pressure
The air handler is equipped with an adjustable static pressure
setting. The available settings are shown in the table below.
Model Available ESP [in. WG]
PVA-A12 0.30 0.50 0.80
PVA-A18 0.30 0.50 0.80
PVA-A24 0.30 0.50 0.80
PVA-A30 0.30 0.50 0.80
PVA-A36 0.30 0.50 0.80
PVA-A42 0.30 0.50 0.80*
*PVA-A42 in Downow External Static pressure: 0.70
The air handler will be set to 0.50 ESP from the factory.
The air handler’s static pressure can be changed through the mode/
function settings in the controller. Please refer to the installation
manual for the controller on how to change this option. Depending
on the controller used, the mode/function will be either 08 for mode
(PAR-31 & Simple MA) or 108 for function (MHK1). Please notice
there are different settings when installing the air handler in the
downow position.
Vertical, Horizontal Left, Horizontal Right External Static
Pressure Setting
External Static
Pressure
Setting No. of
Mode/Function
08/108
Setting No. of Mode/
Function 10/110
(Factory Setting)
0.3 in. WG [75Pa] 1 1
0.5 in. WG [125Pa]
(Factory Setting)
2 1
0.8 in. WG [200Pa] 3 1
Downow External Static Pressure Setting
External Static
Pressure
Setting No. of
Mode/Function
08/108
Setting No. of
Mode/Function
10/110
0.3 in. WG [75Pa] 1 2
0.5 in. WG [125Pa]
(Factory Setting)
2 2
0.8 in. WG [200Pa]* 3 2
*PVA-A42 in Downow External Static pressure: 0.70
Locate the CN4F connector on the
control board. Carefully remove the
connector with the jumper from the
board. Cut the jumper on the CN4F
connector and wire a normally
closed safety oat switch across
the wires. Carefully reinstall the
connector back on the board.
When the Normally Closed Float
Switch opens, the Indoor unit will
turn off.