PVA Installation Manual
Table Of Contents
- PVA-A12, 18, 24, 30, 36, 42 AA7
- Contents
- 1. Dimensions
- 2. Inspect shipment
- 3. Safety precautions
- 4. Indoor unit accessories
- 5. Selecting an installation site
- 6. Combining indoor units with outdoor units
- 7. Installing the unit
- 8. Duct connection
- 9. Mount positions
- 10. Air filter
- 11. Refrigerant piping work
- 12. Drain connections
- 13. Electrical wiring
- 14. Test run
- Table des matières
- 1. Dimensions
- 2. Vérification de la livraison
- 3. Consignes de sécurité
- 4. Accessoires de l’appareil intérieur
- 5. Sélection de l’emplacement d’installation
- 6. Combinaison des appareils intérieurs avec des appareils extérieurs
- 7. Installation de l’appareil
- 8. Raccordement des conduits
- 9. Positions de montage
- 10. Filtre à air
- 11. Mise en place des tuyaux de réfrigérant
- 12. Raccords d’évacuation
- 13. Câblage électrique
- 14. Essai de fonctionnement
- Back Cover
22
13.2. Connecting line voltage
Make sure power supply is off.
The unit should be installed by a licensed contractor/
electrician. If required by applicable national, state and local
codes; a disconnect switch will need to be installed when the
indoor unit is powered from the outdoor unit.
NOTE: If the air handler will be installed with electric heat
package do not power the electric heat from the outdoor unit.
All wiring must conform to National and Local codes
Function Table
Mode Settings
Mode (function) No.
Setting
no.
Initial
setting
Check
Wired remote controller
(RF thermostat)
Power failure auto
restart
Not available
01
(101)
1
1
Available 2
Indoor temperature
detecting
Indoor unit operating average
02
( - )
1
1Set by indoor unit’s remote controller 2
Remote controller’s internal sensor 3
LOSSNAY
connectivity
Not Supported
03
(103)
1
1
Supported (indoor unit is not equipped with outdoor air intake 2
Supported (indoor unit is equipped with outdoor air intake 3
Power voltage
240V (230V)
04
(104)
1
1
220V (208V) 2
Filter sign
100 Hr
07
(107)
1
32500 Hr 2
“No lter sign indicator” 3
Humidier control
Heat operation & Thermo ON
16
(116)
1
1
Heat operation 2
Heater Control
Heater Not Present
11
(111)
1
1
Heater Present *1 2
Heater control during
defrost and error
Disable heater during Defrost and Error
23
(123)
1
1
Enable heater and fan during Defrost and Error *2 2
*1 While the heater is on, the fan will operate at high speed regardless of the fan setting on the remote controller
*2 Heater will not operate during all error modes. Heater will only operate during a communication error between indoor unit and outdoor unit
Note: When CN4Y is used the fan is off when CN24 is energized which is only for use with supplemental heat that is not in the duct.
By setting the Mode No. 23 in the Function Table in section 9-1, the following patterns of fan control will become possible.
Fan control patterns
* If a heater is installed in the duct, do not use Panel heater connector. By doing so, the fan will turn off
when the heater is on, which may result in fire.
*1 While the heater is on, the fan will operate at high speed regardless of the fan setting on the remote controller.
*2 While the heater output is on in the Function Ta ble in section 9-1, the heater will be ON except when the unit is in
communication error, return air thermistor error and motor error.
Fan in defrost Fan(All modes other
than defrost)
Factory
setting
CN4Y for FAN control
(PAC-YU25HT)
Mode(function)
No.23(123)
Disabled
(CN4Y cannot be used with this unit)
1
2
STOP(Heater OFF)
STOP(Heater OFF)
Set(Heater ON
*2
)
High
*1
(Heater ON
*2
)
-
- Please see section 13.4. for external static pressure settings.
1. Remove the desire knockout on the air handler.
2. Attach a conduit pipe connector to the air handler and route the
wiring as shown in the above diagram. Ensure conduit connection
hole is air tight and add a sealant if necessary.
3. Firmly tighten all of the terminal screws. After tightening, verify that
the wires are tightly fastened.
Electrical Characteristics
Symbols : MCA : Max. Circuit Amps ( = 1.25 × FLA) FLA : Full Load Amps
IFM : Indoor Fan Motor Output : Fan motor rated output
Model
Indoor Unit
Hz Volts
Voltage
Range
MCA
(A)
Output
(kW)
FLA
(A)
A12
60 208/230V
188 to
253V
3.00/3.00 0.121 2.4
A18 3.00/3.00 0.121 2.4
A24 4.13/4.13 0.244 3.3
A30 4.13/4.13 0.244 3.3
A36 5.5/5.5 0.430 4.4
A42 5.63/5.63 0.430 4.5
Remark:
* Use a ring tongue terminal in
order to connect a ground wire
to terminal.
Grounding Terminal*
Grounding Terminal*
Grounding
terminal*
Disconnect
switch