Service manual
17
→
Control modes
Control details
2. Fan
Remarks
2-3. Thermostat OFF mode
When the thermoregulating function changes to OFF, the
indoor fan operates in [Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
No drain pump operation
However, when the control changes from COOL or DRY
operation, the drain pump operates for 3 minutes.
(1) Initial setting : OFF → HEAT···[last setting]
When changing the mode from exception of HEAT
to HEAT operation. ···[Downward C]
(2) Vane position :
Horizontal →Downward A →Downward B →Downward C→Swing
(3) Restriction of vane position
1 The vane is horizontally fixed for the following modes.
(The control by the remote controller is temporally invalidated
and controlled by the unit.)
•Thermostat OFF
•Stand by (hot adjuster) [Extra low] mode
•Heat defrost mode
3. Drain pump
4. Vane control
(Up/ down vane
change)