Service manual

52
12
SYSTEM CONTROL
1 Group control with
a single remote
controller
(See page 53.)
Unit
Remote
controller
Unit Unit
Many units, installed at different locations, can be started
and controlled with a aingle remote controller. The remote
controller can be mounted in a different location using a
non-polar two-wire cable, which can be extended up to
500m. A maximum of 50 units can be controlled with a
single remote controller. All units operate in the same
mode.
2 Both remote
ON/OFF and indi-
vidual controls
(See page 54.)
w Timer adapter
(PAC-SA89TA-E)
is needed.
Optional
adapter
Remote
ON/OFF
switch
Remote
controller
Relay box
Unit
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled
individually by each remote controller. Duning remote
ON-OFF control, a message of “CENTRALLY CON-
TROLLED” is displayed on the LCD of the remote con-
troller.
This is available for both one unit control and several units
control.
3 Individual control
by grouping
remote controllers
(See page 55.)
Unit
Remote
controller
Unit Unit
By grouping the remote controllers in one place, several
units installed at different locations can be controlled indi-
vidually, and operation conditions of all units are visible
without a special control board. The control method is the
same as that of the single unit with a single remote con-
troller.
4 Multiple remote
control display
(See page 55.)
w Multiple display
adapter
(PAC-SA88HA-E)
is needed.
Unit
Remote controll
display board
Remote
controller
Unit Unit
Several units can be controlled with a remote control dis-
play board. Operation conditions of all the units are visi-
ble with the remote control display board.
Individual control by each remote controller is also possi-
ble.
5 Auto restart func-
tion
(See page 56.)
Circuit breaker
Remote
controller
A unit can be started or stopped with the circuit breaker
on or off.
Remote controller is also available.
With this function, when the power is restored aftar power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)
1. VARIETY OF SYSTEM CONTROL FUNCTIONS